Model 1094B GPS Substation Clock (250 ns)
Combining world-class accuracy with value pricing, Model 1094B delivers as standard the most commonly requested features for substation applications in Arbiter’s line of precision timing products.
Standard features include a 12 channel GPS receiver with typical accuracy to < ±100 ns, two serial communications ports, and four standard outputs supporting both BNC and 5 mm terminal strip connections, selectable to output IRIG-B, 1 PPS or programmable pulse A or B functions. Able to output 5 Vdc, the unit can easily drive multiple loads in parallel, including synchrophasors. GPS Data Backup battery capable of maintaining the real-time clock, almanac and ephemeris data in the case of power loss.
- 19” Rack unit, 1 RU high
- Accuracy < ±100 ns typical; < ±250 ns worst case
- Four outputs configurable for BNC or 5mm terminal strip connectors
- IRIG-B outputs
- 1 PPS output
- One Form C (SPDT) fail-safe relay
- Two RS-232 and RS-422/485 ports available
Produktinformation
Receiver Characteristics
Timing Accuracy
Accuracy Note | Specifications apply at the 1 PPS output, in the presence of Selective Availability (SA), as of date of publication. |
Accuracy UTC/USNO | ± 250 ns peak; < ± 100 ns typical (SA off) |
Satellite Tracking
Twelve (12) channel, C/A code (1575.42 MHz). Receiver simultaneously tracks up to twelve satellites.
Acquisition
- 150 seconds typical, cold start
- 15 minutes, 90 % confidence, cold start
- 40 seconds, with almanac less than 1 month old
- 15 seconds, with ephemeris less than 4 hours old
I/O Configuration
Output Connectors
Four, each with BNC and 5 mm pluggable terminal strip in parallel.
Output Signals
Jumper selectable to high-drive 5 Vdc (250 mA at > 4 V) selectable to:
- IRIG-B00x level-shift,1 PPS orProgrammable Pulse A or B
- IRIG-B12x modulated
- 300 volt MOSFET output.
The MOSFET output is selectable to the same functions as the high drive 5 Vdc output. The MOSFET output is not electrically isolated from instrument common.
Input Connectors
Event A Input:
One opto-isolated event capture input with 100 ns resolution, BNC connector jumper-configurable to 5 Vdc to 12 Vdc, 24 Vdc to 48 Vdc and 120 Vdc to 240 Vdc nominal input. Event input is also jumper-configurable to COM 1 and COM 2 RXD line.
Programmable Pulse Output
Two programmable pulse outputs, PPA and PPB. PPA is available (by a jumper connection) on outputs 1, 2 and COM 1 pin 4 (RS-232) and pins 8 and 9 (RS-485). PPB is available (by a jumper connection) on outputs 3, 4 and COM 2 pin 4 (RS-232) and pins 8 and 9 (RS-485).
Six modes:
- Every 1 second to 60,000 seconds, starts top of the minute
- Hourly at a specified offset
- Daily at a specified time of day
- One shot at a specified time of year
- 1 PPS to 1000 PPS squarewave (PPB only)
- Aux IRIG Mode (PPB only)
Pulse duration is programmable from 0.01 seconds to 600 seconds, except in one-shot mode, where the output is Low prior to the specified time and High thereafter.
Relay Contacts
One, Form C (SPDT) fail-safe, 0.3A at 130 Vdc; jumper selectable to Fault, Unlocked, or Programmable Pulse A (PPA) functions. Fail-safe means the relay indicates ”fault” or ”unlocked” condition with power off.
Interface
Operator
Display |
|
Functions |
|
Status LEDs |
|
Keyboard | Eight keys |
Setup |
|
System
RS-232 | 1200 baud to 38,400 baud; 7 or 8 data bits; 1 or 2 stop bits; even/odd/no parity |
RS-422/485 | Transmit only, to drive multiple devices. Two outputs. Uses extra pins on Com 1 and Com 2. |
Broadcast modes |
|
Connector | 2 Male 9-pin D-sub Com 1 and Com 2(TXD, RXD, AUX IN, AUX OUT) |
Power Requirements
Standard
Voltage | (Option 07) 85 Vac to 264 Vac, 47 Hz to 440 Hz, 20 VA maximum or 110 Vdc to 370 Vdc, 15 W maximum |
Inlet | (Option 07) IEC-320 with fuse and mating cordset. Specify option P01 – P10
Available cordset plug style and specifications are described in the Options and Accessories section. |
General
Physical
Size | 1 RU rack mount or tabletop, 260 mm deep FMS, Rack mounts included. 508 mm x 381 mm x 203 mm (20 in x 15 in x 8 in), shipping |
Weight | 2 kg (4.5 lbs), net 5.5 kg (12 lbs), shipping |
Antenna | Cable Connection: F-type Size: 80 mm hex (across flats) x 84 mm tall (3.2 in x 3.3 in), including connector Weight: 170 g (6 oz) |
Antenna Cable | Type: RG-6, 15 m (50 ft) provided Weight: 0.69 kg (1.52 lbs) per 15 m |
Antenna Mounting | 0.75 in pipe (1 in – 14 marine) thread |
Environmental
Temperature | Operating: 0 °C to + 50 °C (- 20 °C to + 70 °C typical)
Nonoperating: – 40 °C to + 85 °C |
Humidity | Noncondensing |
EMC | Radiated susceptibility: passes walkie-talkie test.
Conducted emissions: power supply complies with FCC 20780, Class A and VDE 0871/6.78 Class A. Surge withstand capability (SWC), power inlet: designed to meet ANSI/IEEE C37.90-1 and IEC 801-4 |
Certificates and Approvals
CE mark/label and certificate